Automatic Biomass
Boilers 
SMART 100 kW

 

 

  

 

 

 

 

 

 

 

• Fully automatic, ecologic boilers with excellent features • Technical solution flexibility • Multiple fuel possibility • Economical and ecological operation • 3 boilers in range • Efficiency 90 % • Output modulation 30–100 % • Lambda sensor • Stainless Steel Burner with Cleaning Mechanism • Low Maintenance & Service requirements • Heating circuits regulation • Cascade installation solutions • Mobile phone control • Internet control • Mobile container solutions • Special boiler accessories

 

SMART Boilers Application Options:

Extensive Houses

And Smaller-Scale:

Apartment Buildings
Multifunctional Buildings
Sports Complexes
Production Plants & Industrial Premises & Storage Premises
Agriculture & Aquaculture & Horticulture Farms
Hotels/Motels/Wellness Centres/Pools/Sport Arenas
Municipality Buildings
Schools, Hospitals, Police & Army Complexes

 

SMART BOILERS OPERATING DATA
Technical data of the boiler  
Marking   100
Nominal power Pn  kW 100
Partial load Pmin  kW 29
Boiler efficiency at Pn % 88,2
Boiler efficiency at Pmin % 87,7
Boiler class    5
Noise level dB < 65
Weight kg 1042
Water  
Volume of water  l 105
Diameter of water connection  “ 2
Diameter of water connection DN 50
Hydraulic boiler loss attemperature gradient of 10° mbar 47
Hydraulic boiler loss attemperature gradient of 20° mbar 11,9
Boiler temperature °C  65–90°
Minimal temperature of returnable water °C 55
Maximal operational pressure bar 3,5
Test pressure bar 6
Hearth temperature °C  
Hearth pressure mbar -0,01
Required chimney draught mbar 0,2
Need for artificial draught   yes
Flue gas temperature at Pn °C 205
Mass flow rate of flue gas at Pn °C 105
Flue gas temperature at Pmin kg/h 300
Mass flow rate of flue gas at Pmin kg/h 99
Volume of flue gas at Pn m3/h 235
Volume of flue gas at Pmin m3/h 77,6
Smoke pipe diameter mm 200
Chimney diameter mm 200
Type of chimney   Moisture – resistant
Fuel    
Maximum size cm 3
Maximum moisture content % 30
Electric equipment
Connection    
Total W 3131
Ingress Protection Rating (IP)   41

 

 

 

Photo Gallery