Smart Airflow Unit
  
 
Smart Airflow Unit Delivery Description:
250 kg fuel store including fuel auger
 2 000 mm 3-layers chimney set
 Hot-Air fan unit with 0–270 degree movement range
 Circulation pump
 Drain valve
 Pressure control
 Expansion tank
 Pressure release valve
 Automatic control vent
 Heat meter – Optional
 Special Operation Visualisation:
   | 
   | 
Smart 30/50/80 kW Wood Pellet Boiler Features:
 
 
 
 
 
 
 
 
 
 
 
Installation Space Requirements:
  ![]()  | 
 ![]()  | 
|
| Thermal and technical parametres | Unit | AirFlow 30 kW | AirFlow 50 kW | 
| Rated output | kW | 29 | 49,5 | 
| Output range | kW | 8,6 – 29 | 14,6 – 49,5 | 
| Fuel consumption | kg x hrs-1 | 1,9 – 6,6 | 3,44 – 11,63 | 
| Effecienty (rated output) | % | 90,9 | 90,4 | 
| Flue Gas temperature rated output | °C | 94 – 148 | 110 – 153 | 
| Class of the boiler | 5 | 5 | |
| Burning time min/rated output (based on fuel storage of 250 kg)  | 
hours | 147 – 42 | 80 – 24 | 
| Technical parameters of products | |||
| Weight | kg | 815 | 920 | 
| Water content | litres | 140 | 190 | 
| Flue duct diameter | mm | 150 | 160 | 
| Dimension (widthxdept) excluding ash box | mm | 1130 x 1900 | 1130 x 1900 | 
| Maximum water presure | bar | up to 3 | up to 3 | 
| Required fl ue draught | mbar | 0,1 – 0,2 | 0,1 – 0,3 | 
| Recommenteded operating temperature  of heating water  | 
°C | 60 – 80 | 60 – 80 | 
| Lowest temperature of incoming water | °C | 55 | 55 | 
| Sound power level | dB | 57 | 57 | 
| Output power 70/50 °C, 10 °C | kW | 32,48 | 53,91 | 
| Air circulation range in open space | m | 22,5 | 17,5 | 
| Middle level of sound pressure | dB | 64,5 | 67,2 | 
| Electrical parametres of products | |||
| Connection voltage | 230 VAC ±10%, 50 Hz ± 2 Hz | 230 VAC ±10%, 50 Hz ± 2 Hz | |
| Maximum electrical input – ignition | V | 1200 | 1200 | 
| Electrical protection of the control unit | IP54 | IP54 | |
| Electrical protection of the boiler wiring | IP20 | IP20 | |
| Fuel and it s parametres | |||
| Wood pellets diameter | mm | 6,0 – 8,5 | 6,0 – 8,5 | 
| Calorific value | MJ/kg | approximately 16 – 18 | approximately 16 – 18 | 
| Water content | Up to 10% | Up to 10% | |
| Ash content | Up to 1% (0,8 – 1,0%) | Up to 1% (0,8 – 1,0%) | |
                                            